Abstract

The electromagnetic environment of UHV project keeps a close relationship with the environment protection and project cost, so it would catch the full attention after its operation. To well research the electromagnetic environment level and discipline of UHV AC transmission line, a detailed test in the widen areas was carried out, including power frequency electric field, power frequency magnetic field and radio interference. The results showed that, the measurement values of power frequency electric and magnetic field were basically the same as theoretical calculation results. The distribution of radio interference was consistent with the calculation result, but there were differences in the quantity. The actual radio interference level was 2.5-4.5dB(μV/m) lower than the calculation result by CISPR generation function formula. By comparing with fair-weather and foul-weather, radio interference in the condition of fair-weather was 16-19dB (μV/m) less than that in light rainy day.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.