Abstract
To assess the electromagnetic environment (EME) of high-voltage AC transmission lines (TLs) across agricultural greenhouses (AGs), a program that can calculate the power frequency electromagnetic field (PFEMF) under various AC TLs is compiled based on the principle of the simulated charge method and the simulated current method, and the power frequency electric field (PFEF) and magnetic field (MF) strength of AGs are calculated and compared with the field measurement results. The results show that the field measurement values of PFEF intensity and magnetic induction intensity in AGs do not exceed the standard requirements of 10kV/m and 0.1mT. The existence of AGs has a certain influence on the electric field (EF) distribution, but has little influence on the power frequency magnetic field (PFMF). For the PFEF and PFMF in AGs, the numerical calculation results are basically consistent with the field measurement results. The above results provide a reference for the EME assessment of high-voltage AC TLs across AGs.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.