Abstract
The mathematical model of automatic short-circuit calculation is proposed, that is directly used in coal mine high-voltage grid. The model combinates incidence matrix with short-circuit calculation in mine high-voltage grid. According to the connectivity of single-direction graph, the model describes the power supply relation matrix of branches node in coal mine high-voltage grid by the incidence matrix of bus node and branch node. The short-circuit calculation of all short-circuit points is achieved, according to the short-circuit matrix of three-phase and two-phase short-circuit current in all short circuit points given by the model. The analysis results show that the model can realize automatic short-circuit calculation accurately in coal mine high-voltage grid, and it provides a foundation for studying the performance of automatic short-circuit calculation and adaptive setting calculation of multiple fault operation mode.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.