Abstrac t—The paper proposes a measurement method for obtaining the parameters needed to calculate a reliable indicator of the state of transformer core saturation. The major nonlinear effects in transformer core are saturation, eddy current and hysteresis. Saturation is the predominant effect in power transformers, followed by eddy current and hysteresis effects. In saturation, a transformer core act as a source of current generating harmonics, some of which will flow directly toward the primary and secondary windings. The method is based on magnetization current, harmonic content and power factor evaluated of the transformer no-load current with high magnetic flux density subjected. The investigation is done on single phase model core type transformer. The transformer is connected to variable voltage variable frequency (VVVF) source and the investigation is done on various flux densities. The results show that the magnetization current and harmonic content increase significantly when high magnetic flux densities are injected and vice versa with power factor that decrease sharply. These phenomena can be used as the indication of transformer core saturation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.