Abstract
SUMMARYThis paper presents an intensive discussion on a long‐distance high‐voltage direct‐current (HVDC) transmission system that combines two modular multilevel cascade converters based on double‐star chopper cells (MMCC‐DSCC) with DC power cables. Hereinafter, a single MMCC‐DSCC is referred to as a DSCC converter or just as a DSCC for the sake of simplicity. The HVDC transmission system is required to provide low‐voltage‐ride‐through (LVRT) capability to enhance transmission system availability. This paper proposes a new LVRT method without any direct information exchange between the two DSCC converters. The validity of the method is verified, using simulated waveforms from the software package of “PSCAD/EMTDC” and experimental waveforms from a three‐phase 200‐V, 400‐Vdc, 10‐kW, 50‐Hz downscaled HVDC system with a set of 300‐meter‐long DC power cables.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.