Abstract

This paper presents an intensive discussion on a long-distance high-voltage direct-current (HVDC) transmission system combining two modular multilevel cascade converters based on double-star chopper cells (MMCC-DSCC) with dc power cables. Hereinafter, a single MMCC-DSCC is referred to simply as a DSCC converter. HVDC transmission systems are required to provide low-voltage-ride-through (LVRT) capability to enhance availability. This paper proposes a new LVRT control method without any direct information exchange between the two DSCC converters. The validity of the control method is verified by simulated waveforms from the software package of PSCAD/EMTDC and experimental waveforms from a three-phase 200-V, 10-kW, 50-Hz downscaled HVDC system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.