Abstract

This paper presents an intensive discussion on a high-voltage direct-current (HVDC) long-distance transmission system combining two modular multilevel double-star chopper-cells (DSCC) converters with dc power cables. Hereinafter, each converter is referred to simply as a DSCC converter, or just as a DSCC for more simplicity. Such an HVDC transmission system is required to provide low-voltage-ride-through (LVRT) capability to enhance system availability. This paper proposes a practical LVRT control characterized by the use of power-line communications between the two DSCC converters. The validity and effectiveness of the LVRT control is verified not only by simulated waveforms obtained from the software package “PSCAD/EMTDC” but also by experimental waveforms from a three-phase 200-V, 400-Vdc, 10-kW, 50-Hz downscaled system with 300-m-long dc power cables.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.