Abstract
A VSC-MTDC (multi-terminal dc) system consists of voltage-source converters (VSCs) connected to a dc network at their dc terminals. The MTDC is most vulnerable to a dc fault which paralyses all the VSCs until the dc fault is cleared. As dc circuit breakers are expensive, this paper proposes a solution based on extinguishing the dc fault current by opening all the ac-circuit breakers (ac-CBs) which the VSCs are already equipped with on the ac-sides. However, it is necessary to identify which dc line is the faulted line (in case it is a permanent fault) so that it can be isolated by fast dc switches (which are much more economical than the dc circuit breakers), prior to restoring the MTDC system by re-closing all the ac-CBs. This paper presents the handshaking method, which locates and isolates the faulted dc line and restores the MTDC without telecommunication.