Abstract
The special requirement of a PV farm lightning shielding system is that it should not introduce shadow on the active PV surfaces so as to avoid impaired PV generation output. By using a simple, repeatable-unit PV row made up of single or multiple PV strings, the problem of finding a cost-effective and efficient PV row lightning finial arrangement can be resolved. The shading analysis combined with the MS IEC 62305 implementation of the Rolling Sphere Method (RSM) is able to give a simple procedure that lends itself to spreadsheet calculations pertaining to PV farm lightning shielding design.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Journal of The Institution of Engineers, Malaysia
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.