Abstract

This paper compares the potential of lighting energy savings in office rooms by using different control systems, for three locations in Europe and the four main orientations. The method is based on DAYSIM simulations to perform daylight calculations, on laboratory measurement to evaluate precise system energy consumptions and on the implementation of a new algorithm to simulate a close-loop daylight dimming system. It appears that the control of the electrical power in function of daylight leads to very high savings; they slightly depend on the room orientation and the location. Savings vary from 45 to 61%. The performances of an occupancy sensor are also tested. Threshold values of occupancy rate for which daylight dimming leads to higher gains than an occupancy control system vary between 27 and 44% depending on location and orientation. The measurements of the energy consumption of the sensors and detectors also permit to conclude that systems with embedded DALI-compatible ballast controllers should be abandoned in favour of a centralized DALI-compatible ballast controller or embedded analogue systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.