Abstract

In this paper, the kinetic characteristics of high voltage power transformer under short-circuit operation are simulated and the influence of prestress is analyzed for the winding stability. Firstly, the finite element method (FEM) is applied to calculate the leakage magnetic field of transformer and electromagnetic force of windings. Secondly, the axial electromagnetic force under short-circuit condition acts on the transformer windings, which are regarded as complex viscoelastic system. The characteristics of the vibration responses, such as dynamic displacement and dynamic force, are illustrated and their frequency responses are analyzed. Finally, the relationship between prestress and peak value of dynamic force, and as well as displacements of each pancake coil, are discussed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.