Abstract

To analyze the influence of liquid spraying flow rate on the performance of a falling-film evaporator with R134a, the finite difference model of the horizontal-tube falling-film evaporator is established, and a falling-film air-cooled water chiller with ejector liquid recirculation system (LRS) is presented; then the comparison between numerical simulation and experimental tests are performed. The analysis results show that the experimental and numerical evaporating capacities increase 9.5% and 6.7%, respectively, when the liquid recirculating ratio Rl increases from 1.0 to 1.21; and the deviation between the experimental and numerical capacities of the evaporator is about 3.3%. And that the evaporated liquid flow rate rises quickly at first and then increases slightly as Rl increases. Moreover, the results show that the optimum value of Rl is about 1.2, the corresponding value of integrated falling-film factor φ with about 0.85. This suggests that attempting to eliminate completely the dryout patch outside of tubes is unadvisable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.