Abstract
Impulse performance of grounding grid is needed for lightning protection design of power system. This paper describes an impulse test facility established for the full-scale grounding grid (50 m long and 52.5 m wide) in a 110 kV substation. Test method is presented, including configuration of current injection and return point, measurement of potential rise and longitudinal current. Impulse test is carried out with 2.6/50 and 8/20 μ s current waveform, and the maximum current amplitude is 4 kA. A Current Distribution, Electromagnetic fields, Grounding and Soil structure simulation for the tested grounding grid is also adopted. Impulse performance of full-scale grounding grid is affected by soil ionization and conductor inductance. There is steeper peak on the potential rise waveform near the injection point with shorter wave front current, which leads to more uneven potential rise distribution. Partial soil ionization could increase the current dispersing into the soil at partial area of the grounding grid, and the longitudinal current flowing to the next area decreases. These two factors pose a high potential difference hazard to the secondary equipment via the secondary cable.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have