Abstract

PurposeThe purpose of this paper is to recover the waste heat of flue gas heat exchanger (FGHE) as efficiently as possible and avoid the acid dew corrosion of that.Design/methodology/approachA novel flue gas waste heat recovery system was proposed in the paper. The dynamic mathematical models of key equipment in that were established based on theory and experiment method. The proportion integration differentiation-differentiation (PID-P) cascade control method based on particle swarm optimization algorithm was used to control the outlet temperature of FGHE. The dynamic characteristics of the flue gas heat exchange system were simulated by the particle swarm optimization algorithm with different fitness functions.FindingsThe PID-P temperature controller parameters can be quickly and effectively obtained by the particle swarm optimization algorithm based on the fitness function of integral time absolute error (ITAE). The overshoot, rise time and adjusting time of the novel system are 2, 83 and 105s, respectively. Compared with the traditional two-step tuning (T-ST) method, the novel system is better in dynamic and steady-state performance. The overshoot and the adjustment time of the system are reduced by 44% and 328s, respectively. ITAE is a performance evaluation index for control system with good engineering practicability and selectivity.Originality/valueThe dynamic mathematical model of key equipment in the new flue gas waste heat recovery system is established and the system's control strategies and methods are explored.

Full Text
Published version (Free)