Abstract

The main results of a theoretical and experimental investigation of the performance characteristics of an ejector and an ejector refrigeration machine (ERM) operating with refrigerant R245fa at design and off-design working conditions are presented. The ejector and ERM were explored theoretically using improved 1D model and the calculated results were validated experimentally on ejector test rig that has been assembled and operated at National Taiwan University. For typical cases, the performance characteristics variation with condensing, generating and evaporating temperatures along with performance maps are presented. The theoretical results are compared with the results of a set of experiments and good qualitative and quantitative agreement is observed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.