Abstract
Since the majority of vacuum circuit breakers in use are of the single-break variety, there have been few studies of double-break vacuum circuit breakers. This report describes our investigations of the interruption characteristics of the double-break vacuum circuit breaker. In this investigation, the post arc current and recovery voltage distribution ratio were measured in order to clarify the relationship between them. The results show that a bias of the voltage distribution ratio occurs when the post arc current value becomes imbalanced. In addition, the measurements of the post arc current for circuit breakers with spiral contacts are very scattered as compared with those with axial magnetic field contacts. Normally, the double-break vacuum circuit breaker consists of two contacts of the same type. However, when two spiral contacts are used, the scattering of post arc current causes a current imbalance. As a result, a bias of the voltage distribution ratio may occur. It appears to be preferable to use double-break vacuum circuit breakers with axial magnetic field contacts.