Abstract

Paralleled high-voltage SF6 circuit breakers with a highly coupled split reactor (HCSR) could realize the function of automatic current-sharing and current-limiting. Aiming at investigating the arc characteristics of paralleled SF6 circuit breakers with an HCSR, the single-phase tests for the paralleled high-voltage SF6 circuit breakers with an HCSR were carried out, including the opening and closing–opening operations. The influence of the capacitor paralleled to one of the breaks was studied. A mathematical model was developed for the paralleled high-voltage SF6 circuit breakers with an HCSR by coupling the equivalent circuit equations into the magnetohydrodynamic (MHD) arc model through the embedded codes, laying the foundation for the further research. The variation of the short-circuit currents in the branches during the breaking process was analyzed in detail. The current-sharing and current-limiting effects are quite satisfying. The temperature distribution of both arc chambers was presented. The calculated results were in agreement with the experimental results to some extent.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.