Abstract

We optimized the internal structure (heat exchanger areas) of a dynamic vapor compression refrigeration system for maximum global system performance described by the coefficient of performance (COP), refrigeration rate, second law efficiency, and pull-down time. The numerical optimization was subjected to fixed system heat transfer surface, and the relative sizes of condenser and evaporator were selected optimally via parametric sweeps. Optimization results demonstrated the existence of distinct optimal area allocation for each objective function considered herein while higher evaporator to condenser global heat transfer ratio was preferred in all cases. Maximum COP was achieved, for instance, with smaller evaporator area than maximum second law efficiency that yielded shorter pull-down time and lower refrigerated space temperature in exchange for slightly higher compressor power and total exergy destruction. In summary, this work provides insights into the selection of an optimal refrigeration system design based on its dynamic responses and physical implications.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.