Abstract
This research article deals with a Hybrid cascade refrigeration system (HCRS) comprising of vapor absorption refrigeration system (VARS) at the top or high temperature stage and vapor compression refrigeration system (VCRS) at the bottom or low temperature stage in a two-stage cascade refrigeration system using a mathematical model for energy and exergy analysis. The theoretical analysis is carried out taking H2O-LiBr solution in VARS and R134a, R32, R1234yf in VCRS as refrigerants. The three refrigerants (R134a, R32 and R1234yf) in this study are selected because these refrigerants have been recommended as future alternative refrigerants due to their zero ODP and low GWP properties. It has been found that the optimum generator temperature of HCRS is same for all the three eco-friendly refrigerants at which maximum coefficient of performance (COP) and maximum exergetic efficiency occurs. Further it is observed that the performance of the system considered in the study is better with R134a in comparison to R32 and R1234yf as refrigerants in the VCRS and R32 exhibits better result when compared with R1234yf.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.