Abstract

After stating the reasons leading to EDF's interest in 420 kV GIL and the technical and economic imperatives to be considered, the principles adopted for the insulation co-ordination of 420 kV GIL up to a few tens of kilometers long are described. All the insulation coordination approach is based on the global failure rate requested for GIL taking into account: the gap in term of reliability between the actual technology of GIS and the one needed for reliable GIL, the dielectric characteristics of the N 2 /SF 6 mixtures selected, the specific features of GIL with regard to insulation co-ordination (many insulations in parallel, on-site dielectric tests at reduced levels, etc.) compared to substation equipment, the withstand voltage guaranteed for the whole GIL by the type tests and on site tests.

Full Text
Paper version not known