Abstract
This paper has researched the insulation characteristics of 10% c-C4F8/N2/CO2 mixtures under lightning impulse voltage by experiment. It is shown that the positive and negative lightning impulse breakdown voltages of 10%c-C4F8/N2/CO2 gas mixtures rise linearly as the electrode gap distance and gas pressure increase and under the same conditions, the positive lightning impulse breakdown voltage of the gas mixtures is always higher than the negative lightning impulse breakdown voltage. As the gas mixtures have a little higher liquefied temperature than SF6 and the comprehensive GWP is about 5% of SF6, and the positive and negative lightning impulse breakdown voltages can both reach 60% of SF6, 10%c-C4F8/N2/CO2 gas mixtures can be applied as insulation gas in electrical equipment such as C-GIS, GIT, GIL and so on.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.