Abstract

Inline chlorination technologies can provide a flexible option for water treatment in a variety of scenarios in low-resource settings. However, limited efficacy data on chlorine dosing and the resulting free chlorine residual (FCR) levels under controlled conditions increases the barrier to use for both field practitioners and end users. In this paper, we report FCR data on the Aquatabs Flo device, a passive inline chlorinator, for common operating conditions including flow rates between 2 and 18 L/min (0.5 and 4.8 gal./min), pressure levels between 137.9 and 551.6 kPa (20 and 80 psi), and device positions (horizontal, tilted left or right, leaning forward or backward). In addition, we demonstrate a modification to the device to enable point-of-collection applications. Results suggest that variations in pressure do not influence FCR values, whereas device positions (i.e., misalignments) do. Finally, device modifications can reduce the FCR values for point-of-collection applications. The data reported here can be used to build decision support tools for field practitioners.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.