Abstract

The installation of a raised floor system can change the thermal behaviour of the building by reducing the interaction between the heat gains and the thermally massive concrete slab. In this study, the influence of the raised floor on the summer design day zone cooling load profile is evaluated with EnergyPlus for an office building located in San Francisco. The effects of structure type, window-to-wall ratio and the presence of carpet on the thermal behaviour of the raised floor are also investigated. The results show that the mere presence of the raised floor largely affects the zone cooling load profile and the peak cooling load over the range of −7 to +40%. The most significant parameters are the zone orientation, i.e. the exposure to direct solar radiation, and the presence of floor carpeting. If carpeting is present, commonly used in U.S. office buildings, the overall impact on zone peak cooling load is reduced, ranging from 0 to 5% greater for the raised floor than without it. Without carpet the peak cooling load is 4% greater with raised floor than without it in the north zone, 22% in the east and west zones, and 12% in the south zone.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.