Abstract

In the current context of a world energy situation that demands high-quality indoor environments compatible with rational energy use, the purpose of this work is to present a successful case study of a comfortable low-energy office building in Madrid, Spain. An exhaustive indoor air quality and thermal comfort field measurement survey was carried out during the summer period. The main global and local thermal comfort parameters in several workplaces, as well as CO2 concentration in supply air, exhaust air, and occupied space, were registered. Correct operation of the demand-controlled ventilation system and air distribution is observed. Also, thermally activated building systems and shading design make it possible to get high levels of indoor thermal comfort, as derived from measurements. This proves that the integration of novel energy-efficient concepts in office building design can not only contribute to a minimization of the energy use but can simultaneously favor the achievement of high indoor environmental quality.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.