Abstract

Ground source heat pump systems have been proved to be one of the most efficient systems for heating and cooling in buildings. However, an optimal energy performance depends on a good control of the auxiliaries, which stand for an important part of the total energy consumption. The authors previously developed an experimental in situ optimization methodology for the water circulation pumps frequency of ground source heat pump systems when single stage and multi-stage ON/OFF regulation is employed. However, the user comfort was not completely met under extreme weather conditions during summer. This paper presents the upgrading of this energy optimization strategy combining circulation pumps frequency variation and building supply temperature compensation in order to ensure the user comfort while keeping high energy savings. Experimental results show that the user comfort is met by means of this new methodology and the energy savings (33%) are even higher than those obtained with the previous methodology.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.