Abstract

Coagulant dosing control in drinking and wastewater treatment plants (WWTPs) is often limited to flow proportional concepts. The advanced multi-parameter-based dosing control systems have significantly reduced coagulant consumption and improved outlet qualities. Due to the long retention time in separation stages, these models are mostly based on feed-forward (FF) models. This paper demonstrates the improvement of such models with feed-back (FB) concepts with simplifications, making it possible to use even in systems with long separation stages. Full-scale case studies from a drinking water treatment plant and a WWTP are presented. The model qualities were improved by the dosage adjustment of the FB model, ranging from 66% to 197% of the FF model. Hence, the outlet qualities became more stable and coagulant consumption was further reduced in the range of 3.7%-15.5%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.