Abstract

Islanding detection is a mandatory function for grid-connected converters. The popular slip mode frequency shift (SMS) and auto phase shift active islanding detection methods are investigated and an improved (IM)-SMS strategy is proposed in this study. In the proposed method, additional phase shift is introduced to help in stimulating the action of the islanding detection and the algorithm is simplified as well. When the utility grid is disconnected, the algorithm keeps the frequency of the converter output voltage deviating until the frequency protection relay is triggered. The working principle of the method is introduced and the guidance of parameters selection and optimisation is also provided. The islanding detection performance is evaluated through theoretical analysis and verified by digital simulation and experimental results. The IM-SMS method exhibits features of simplicity, easy implementation and high reliability.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.