Abstract

Islanding detection is a mandatory feature for grid-connected inverters. The effectiveness of passive islanding detection methods (IDMs) is usually demonstrated by means of nondetection zones (NDZs) represented in a power mismatch space (/spl Delta/P versus /spl Delta/Q). Active frequency drifting IDMs have been shown to provide improved performance but their theoretical NDZ cannot be described in the /spl Delta/P versus /spl Delta/Q space for a general RLC load. This paper shows that a load parameter space based on the values of the quality factor and resonant frequency of the local load (Q/sub f/ versus f/sub 0/) can be used in these cases. It employs a single curve to represent the NDZ of frequency drifting IDMs for any RLC loads. Equations that represent NDZs of three common active IDMs in the Q/sub f/ versus f/sub 0/ load parameter space are derived and it is shown that the slip mode frequency shift and the Sandia frequency shift IDMs can be designed to guarantee islanding detection for equivalent RLC loads with a quality factor smaller than a design value. The accuracy of the NDZs is verified with simulation and experimental results.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.