Abstract
according to analysing the generation principle of transformer winding deformation and its impact on the vibration signal, and make a large number of trial, it can be found in addition to the fundamental frequency component that can reflect the failure, the new characteristic frequency which conclude 50Hz frequency component and some of its harmonic components, the harmonic components of the fundamental frequency can also reflect the failure. Transformer winding deformation fault diagnosis method is proposed based on the relationship between the characteristic frequency, it can not only diagnose whether the failure inside the transformer windings, but also determine the type of fault. In order to verify the proposed method, deformation fault is set to the actual transformer winding. After de-noising, discounted processing, the acquisition monitoring points of vibration signal is used by the proposed method, and the actual transformer is diagnosed, The diagnostic result is same with actual failure. It is shown that the proposed diagnostic method is accurate and feasible.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.