Abstract

The paper proposes an improved approach to cable-fault location, which is essentially based on synchronised sampling technique, wavelet analysis and travelling wave principle. After an outline of the new scheme and brief introduction to the three major techniques, wavelet analysis of faulty transient waveforms is conducted in details to determine the best wavelet levels for this particular application. Then a 400 kV underground cable system simulated by the Alternative Transient Program (ATP) under various system and fault conditions is used to fully evaluate the approach. Numerical results show that this scheme is reliable and accurate with errors of less than 2% of the length of the cable line.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.