Abstract

The main objective of this on-site study is to use a full-scale HVAC (Heating, Ventilating and Air-Conditioning) system installed in an office building in Taiwan for comparing the power consumption, energy-saving, and CO2reduction by variable primary flow (VPF) chilled water systems for controlling the HVAC. The on-site experimental results indicate that average power consumptions are 44,935 kWh for the constant volume (CV) chilled water systems, and 39,025 kWh for the VPF system. Approximately 19% of the maximum energy-saving rate can be achieved if the HVAC system is operated as a VPF system. Additionally, the reduced quantity of accumulated CO2emission varies from 0 to 44,186 kg with 0.623 kg-CO2kwh-1emission factor during the office hours of 08:00 (a.m.) to 20:00 (p.m.). The results demonstrate that switching the operation of an office building HVAC system from CV to VPF will significantly enhance energy savings and CO2reduction. This study is will offer useful information for evaluating an indoor environmental policy with respect to energy savings and CO2emission reduction for office HVACs used in subtropical regions.