Abstract

This paper proposes an improved coordinated control of standalone brushless doubly fed induction generator (BDFIG) supplying nonlinear loads. Due to the existence of nonlinear loads, the voltage at the point of common coupling becomes distorted with a large number of low-order harmonics, which severely degrades the performance of power generation systems. In order to eliminate the included low-order harmonics, a coordinated control method of harmonic mitigation has been presented in this paper for the control of both machine side and load side converters. Then, a weight factor is introduced to the proposed control method for distributing the contribution of harmonic mitigation between the two converters. Comprehensive experimental results on a 30 kVA BDFIG are presented to verify the proposed control method.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call