Abstract

This paper presents a relaying algorithm based on Artificial Neural Network (ANN) technique for the protection of transmission line. A feed forward ANN with six inputs and eleven outputs has been developed for the detection and classification of faults. Data was generated by simulating a 400 kV, 50Hz, 100 km transmission line in PSCAD/EMTDC at a sampling frequency of 2 kHz. Three ANN configurations with different combinations of inputs have been attempted. Initially all the three ANN configurations were trained and tested using truncated data for their comparative performance. ANN-2 configuration has been found to be the best one and has an accuracy of 100% for fault detection and classification in both training and testing phases with the relay operating time of 12.5 ms. ANN-2 has been further trained and tested using full data. Two-fold cross verification was carried out. An accuracy of 100% was obtained on testing with 12.5 ms delay each time.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.