Abstract

Improving network power quality through harmonic reduction requires recognition of Harmonic Sources (HSs) to drive them to compensate their harmonics. This paper proposes a new method for equitable distribution of the Harmonic Compensation Cost of the network among the HSs based on the Harmonic Contribution Matrix. Each element of the Harmonic Contribution Matrix is the harmonic contribution of a specific source to the harmonic voltage of a specific bus. The output of the proposed method is a penalty curve for each HS over time. The amount of the fine estimated for each individual HS per hour is a function of not only the contribution of that HS to the harmonic voltage of different buses, but also the contribution of the Harmonic Compensation Cost from the perspective of each bus, nominal voltage of each bus, and the sensitivity of each bus to the harmonic voltage. The proposed algorithm is evaluated on the IEEE 14-bus network and Esfahan regional electrical power network in Iran. The simulation results demonstrate the capability of the proposed method to allocate the hourly penalty curve to the HSs.