Abstract
This paper presents the performance of distance protection of transmission lines when compensated with shunt Flexible AC Transmission System (FACTS) Controllers/Devices. The performance of distance protection is evaluated for shunt-FACTS Controllers applied for mid-point voltage control. The impact of two types of shunt FACTS Controllers, Static Var Compensators (SVC) and Static Synchronous Compensators (STATCOM) on the transmission line distance protection are studied for different fault types, fault locations and system conditions. The dynamics of the shunt-FACTS Controllers with their associated control systems are considered and simulated using RSCAD/RTDS testing environment. The performance of both the basic/non-pilot distance scheme and a Directional Comparison Blocking (DCB) scheme are evaluated in this paper. The results of the commercial relay testing show the adverse effects of mid-point shunt-FACTS compensation of transmission line on both non-pilot and DCB distance protection schemes.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.