Abstract

AbstractThe reach of primary protection zones of transmission lines distance relays is affected when large power flows circulate through the transmission line prior to a short circuit occurrence. This can cause improper operation of the protection system in certain scenarios. In practice, protection zone adjustments are made by considering the apparent impedances obtained from short‐circuit simulations in the line of interest using standard methods such as IEC 60909‐0 or ANSI/IEEE C37.010. However, these short‐circuit calculation methods omit the existing operating conditions prior to the fault. Therefore, this work proposes a set of equations developed for calculating the apparent impedance seen by the distance relay in view of different types of short circuits, including the effects of power flow prior to the fault. These equations are then used to establish the distance primary protection zone settings. The analysis uses the mathematical expressions proposed of voltages and currents at the relay location, and the impedance diagrams obtained from simulated short circuits. Subsequently, the settings obtained with these equations are compared to those achieved using the IEC 60909‐0 standard, allowing for the differences in settings and their effectiveness. Finally, this procedure is applied to a part of the Ecuadorian Transmission System.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.