Abstract

This paper explores the impact of a transmission-line midpoint STATCOM on the performance of the generator loss-of-excitation (LOE) protection. In this context, investigations are conducted on a two-hydrogenerator power station for two LOE contingencies, namely, a complete LOE due to a field-winding short circuit and a partial LOE due to a sudden drop in the excitation voltage at different generator loadings. The results of these investigations show that the midpoint STATCOM has adverse impacts on the LOE distance relay in the form of delay time and/or underreach phenomenon. These adverse impacts vary with the generator loading and the LOE mode. The time-domain simulation studies are conducted using PSCAD/EMTDC software.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.