Abstract

Instrument Transformers (ITs) are essential devices for all the measurement tasks, f.i. metering, protection and diagnostics, in electricity grids, since they scale voltage and current down to levels compatible with measuring instruments. At the input of Power Quality (PQ) instruments and Phasor Measurement Units (PMUs), inductive voltage and current transformers (VTs and CTs) are still the most used ITs, even if, their performance in presence of disturbances is not fully assessed. This paper analyses the impact of the inductive CTs on the measurement of fundamental synchrophasors, by a PMU, in presence of a particular class of disturbances, the undesired modulations on current signals. Experimental tests, on two different CTs, show that there are critical situations, where, even compensating CT systematic ratio and phase errors, 1) CT exceeds its accuracy class limit and 2) considering the sole contribution of CT, PMU performance stays very close to the error limits of the standards.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.