Abstract

Stiction in control valves is an industry-wide problem which results in degradation of control performance. A new approach to detect the presence of stiction by utilising only the PV-OP data from control loops is proposed using an Adaptive Neuro-fuzzy Inferencing System (ANFIS). Intuitively, the error between the output of an FIS model developed with stiction and a process with stiction would be minimal. When benchmarked against seventeen well-known industrial control loop case studies, the Intuitive ANFIS-based Method (IAM) accurately predicts the presence or absence of stiction in 65% of loops tested.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.