Abstract

A new topologically correct hybrid transformer model is developed for low and midfrequency transient simulations. Power transformers have a conceptually simple design, but behaviors can be very complex. The selection of the most suitable representation for a given behavior depends on the type of transformer to be simulated, the frequency range, and other factors, such as the internal design of the transformer and available parameters or design data. Here, a modular model suitable for frequencies up to 3-5 kHz is developed, utilizing a duality-based lumped-parameter saturable core, matrix descriptions of leakage and capacitive effects, and frequency-dependent coil resistance. Implementation and testing of this model was done for 15-kVA 208Delta-120Y 3-legged and 150-kVA 12,470Y-208Y 5-legged transformers. The basis and development of the model is presented, along with a discussion of necessary parameters and the approaches for obtaining them

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.