Abstract

This paper presents HFC32 average boiling heat transfer coefficients and pressure drops measured inside a small Brazed Plate Heat Exchanger (BPHE): the effects of heat flux, saturation temperature (pressure), and outlet conditions are investigated. The experimental tests were carried out at four different saturation temperatures (5, 10, 15, and 20 °C) and four different evaporator outlet conditions (vapour quality around 0.80 and 1.00, vapour super-heating around 5 and 10 °C). The average heat transfer coefficients show great sensitivity to heat flux and outlet conditions and weak sensitivity to saturation temperature (pressure). The saturated boiling heat transfer coefficients were compared with a new model for refrigerant vaporisation inside BPHE (Longo et al., 2015): the mean absolute percentage deviation between calculated and experimental data is 4.7%. The heat transfer and pressure drop measurements are complemented with a IR thermography analysis for a better understanding of the vaporisation process inside a BPHE.