Abstract

This paper presents the heat transfer coefficients and the frictional pressure drops of R1234ze(Z) and R1233zd(E) boiling inside a commercial Brazed Plate Heat Exchanger (BPHE): the effects of heat flux / mass flux, saturation temperature / pressure, outlet conditions and fluid properties are investigated. The boiling heat transfer coefficients are controlled mainly by heat flux / mass flux and evaporator outlet conditions. The degrees of superheating at the outlet of the evaporator produces a degradation of the average boiling heat transfer coefficient in the whole evaporator, particularly for R1234ze(Z). The frictional pressure drops exhibit a quadratic dependence on refrigerant mass flux. Saturation temperature / pressure has a remarkable influence only on the frictional pressure drops. R1234ze(Z) exhibits boiling heat transfer coefficients higher and frictional pressure drops lower than those of R1233zd(E). There is a reasonable agreement between the saturated boiling heat transfer coefficients and the calculated values by two recent models for boiling inside BPHE.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.