Abstract

The effects upon the performance of plate fin-tube cross flow heat exchangers due to outer surface geometry are considered. The finning parameter varying through 11 to 23, a total of ten geometrically distinct configurations were tested over a Reynolds number range from 100 to 30,000. The tube outside diameter with the collar thickness defines the characteristic dimension. The convective heat transfer coefficients are presented as plots of Colburn j-factor versus Reynolds number and compare well with previous studies. Typical data spread being ±10 percent range, the j-factor, the Reynolds number, and the finning parameter are correlated.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.