Abstract

Three-phase inverter-based multi-bus ac systems could suffer from the small-signal instability issue due to the dynamic interaction among inverters and passive components in the systems. To address this issue, this paper proposes two harmonic stability analysis methods and an inverter controller parameter design approach for stable system operation. The proposed sequence-impedance-based harmonic stability analysis methods can reduce the computation effort by avoiding the calculation of right-half-plane poles of impedance ratios, as compared with the impedance-based analysis method using Nyquist stability criterion. Therefore, the controller parameters can be designed in the forms of stability regions in the parameter space, by repetitively applying the proposed stability analysis methods. In addition, the proposed stability analysis methods enable the system stability by using only measured component impedances. Experimental results of an inverter-based two-area system validate the effectiveness of the proposed stability analysis methods and parameter design approach.