Abstract

The penetration of distributed generation (DG) scheme in modern power system is progressively increasing because of the call for environmental friendly energy resources. Photovoltaic (PV) has been identified as one of such energy resources which can provide reliable and efficient power supply when integrated with distribution network. The installation of a single site PV module is modelled in a bus bar of the 31-bus 330kV network of Power Holding Company of Nigeria (PHCN) to characterize and predict harmonic pattern therein and also to assess bus voltage disturbance in the network due to increase in harmonic emission level. The simulation results obtained using PCFLO version 6 programme platform indicates that the system voltage variation is dependent on harmonic emission level. In a bus bar the highest and constant non-sinusoidal current Total Harmonic Distortion (THD) of 29% flows in the neutral of the apparatus in the candidate bus where the non-linear load is installed irrespective of harmonic current source magnitude.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.