Abstract

Considering that when the photovoltaic inverters are connected to the grid through filters, the harmonic impedance at the photovoltaic side of the common connection points may not satisfy the condition that the harmonic impedance at the photovoltaic side is much larger than that at the background side(which is satisfied in the traditional grid), so that when estimating the harmonic voltage emission level, the influence of the harmonic impedance on the photovoltaic side can not be neglected. A method for evaluating the harmonic voltage emission level considering the harmonic impedance on the photovoltaic side is proposed. Firstly, the harmonic impedance of photovoltaic side is estimated according to the parameters of photovoltaic inverters, filters and lines. Then, the harmonic voltage emission level is evaluated based on the estimated harmonic impedance of photovoltaic side. Finally, the advanced and accuracy of the proposed method is verified by simulation and comparison with other methods.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.