Abstract

This paper presents a general filtering and unbalance compensation scheme for electric traction systems using a direct power control-based algorithm. For a balanced three-phase three-wire system, the proposed method is able to control the power flow exchange between the grid and the load so that the instantaneous complex power is maintained constant. As a consequence, any nonlinear unbalanced load is seen by the three-phase supply as a balanced linear load. The proposed filter is evaluated on power substations with open delta (V-V) and Scott transformer feeders, and for two-level and dual-converter in the power stage. The scheme has been simulated and experimentally validated. The results from experimental and simulation tests show the controller advantages and the applicability of the proposed method in railway systems.