Abstract

Half-Bridge Modular Multilevel Converters (HB-MMCs) are defenseless against DC side faults. Different types of DC Circuit Breakers (DCCBs) assisted with arrester banks/damping resistors such as solid-state CBs and hybrid DCCBs can be used to interrupt the DC fault current. Arrester banks are used to block any overvoltage after interrupting the fault current and in turn to demagnetize the circuit inductors. The main disadvantage of the arresters is that they forcibly break apart when they are overloaded. In this work, an arrester-less DC fault current limiter is proposed for HBMMC configuration. The proposed DC fault current limiter has two pre-charged capacitors in series with transmission poles. These pre-charged capacitors are bypassed during normal conditions, while they are inserted in the DC current path during DC side fault to limit the grid current contribution into the dc fault. The proposed protection scheme is assessed using a simulation study.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.