Abstract

This article reviews and summarizes research conducted during and related to ASHRAE RP-1675, Guidance for Data Center CFD. The ultimate objective is to provide users and vendors of computational fluid dynamics (CFD) tools with best-practice modeling advice to support greater adoption of the technology to design and operate reliable and sustainable facilities. RP-1675 identified and developed good CFD modeling practices by benchmarking CFD simulations against experimental measurements for a “laboratory data center,” considering past and concurrent research, and performing additional sensitivity studies in CFD. This article provides a detailed review of the experimental and CFD work conducted during RP-1675, which focused on the modeling of computer room air handler units (CRAHs) with vertical-axis blowers located in the raised-floor plenum, and modeling perforated floor tiles, and raised-floor stanchions. This article ultimately summarizes current guidance for data-center CFD.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.