Abstract

This paper presents a two-stage grid-connected PV system with reactive power management capability. The proposed model can send phase-shifted current to the grid during a low-voltage ride through (LVRT) to recover the voltage levels of the grid’s feeders. The novelty of the proposed algorithm, unlike the common methods, is that it does not need to disable the maximum power point tracking (MPPT) state while managing active and reactive power injection simultaneously. Moreover, the new method promotes a safety factor by offering overcurrent protection to the PV inverter. The phase-locked loop based on the synchronous reference frame (SRF-PLL) is optimized using a genetic algorithm (GA). The settling time of SRF-PLL’s step response is minimized, and the frequency dynamics are improved to enhance synchronization during LVRT. The system’s performance is tested and verified using MATLAB/Simulink simulations. The obtained results prove the effectiveness of the proposed control algorithm in managing reactive power interventions. The optimized phase-locked loop shows robust performance and is compared to the conventional low-gain PLL to spot the enhancement.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.